Faulty Sakno siliconefoamfirestop installation in a Calgarywastewater treatment plant in the 1980's. This is a hole in a fire-resistance ratedconcrete wall, above a fire door frame. The outside temperature was ca. -40°C (-40 F). The inside was heated. A steady temperature is needed for the foam to "snap", solidify and expand properly, as it evolves hydrogengas. Every now and then someone opened the outside door, the temperature would plummet and the foam's consistency was affected, as can be seen by the tears and uneven bubble distribution and incomplete phase change. To achieve its rating, as per its certification listing, the foam also requires ceramic fibre boards (furnace insulation) to permanently cover both sides of the foam, a common deficiency, exposed by whistleblower Gerald W. Brown. This is image 1 of 2. The other one is right here: http://commons.wikimedia.org/wiki/Image:Silicone_foam_sakno2.jpg .
Το έργο αυτό έχει απελευθερωθεί στην public domain από τον δημιουργό του, I, Achim Hering. Αυτό ισχύει σε όλο τον κόσμο. Σε ορισμένες χώρες αυτό μπορεί να μην είναι νομικά εφικτό. Αν ναι: I, Achim Hering Παραχωρώ σε οποιονδήποτε το δικαίωμα να χρησιμοποιήσει αυτό το έργο "για οποιονδήποτε σκοπό", χωρίς κανέναν όρο, εκτός και αν τέτοιοι όροι τίθενται από την νομοθεσία
This image is very small, unfixably too light/dark, or may not adequately illustrate the subject of the image If a higher-quality version of this particular image is available, please replace this one; otherwise, a supplemental image illustrating this subject and available under a free license should be found or provided and uploaded as a separate file.
Αυτό το αρχείο περιέχει πρόσθετες πληροφορίες, πιθανόν από την ψηφιακή φωτογραφική μηχανή ή το scanner που χρησιμοποιήθηκε για την δημιουργία ή την ψηφιοποίησή της. Αν το αρχείο έχει τροποποιηθεί από την αρχική του κατάσταση, ορισμένες λεπτομέρειες πιθανόν να μην αντιστοιχούν πλήρως στην τροποποιημένη εικόνα.